Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)1 Repair side walls that are pulled away from platform. 2/12/2020
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)2 Front car gate needs repair, must not be more than 1" off floor across entire opening when closed
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)2 Rear car gate has broken slats, replace same
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired, replace or have serviced
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Repair lower 2nd floor door panel for proper clearances
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Repair hoistway door release. Pull chain missing
MO Minimum : Elevators (I) - Pits (I)5 Clean water and debris out of the pit. 11/14/2018
MO Minimum : Elevators (I) - Pits (I)1 Need to clean pit
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 In car signage stating no passengers and freight class not present. 2/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.7 - Car door or gate 8.11.2.1.1(g) Car gate needs repair, must not be more than 1" off floor. 2/19/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.39 - Low Oil Protection 3.26.9 Low Oil Protection (Re-Inspection) Low oil protection shall work. 2/19/2021
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Reinstall protective handrail at edge of machine space that was removed to replace building equipment
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.11.3.1.3(r) Hoistway door astragal at top floor is torn, needs replacement. 2/19/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room