Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 x 2.4.2.1 Where Oil Buffer are used the minimum Runby is 6 inches. Buffers have electrical switches current runby is 2.5 inches. Ropes need shortened. 8/7/2024