Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 x Counterweight Run by less than minimum of 6 inches suspension ropes shall be shortened. 8/7/2024