Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening
MO Minimum : Elevators (H) - Machine Rooms (H)4 There is a laptop and an amplifier in the machine room providing music to the roof top patio that needs to be removed. Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in machine room
MO Minimum : Elevators (I) - Pits (I)1 There is standing water in the pit. The sump pump is not working. All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator.
MO Minimum : Elevators (I) - Pits (I)8 Sump holes, with or without pumps, and well holes that are accessible, shall be covered flush with the pit floor. The covering shall consist of a noncombustible material
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces The machine room needs to be cleaned.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 An ABC fire extinguisher with a current test tag shall be provided in the elevator machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate There is no state operating certificate in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits Clean the pit. 10/2/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state elevator certificate. 10/2/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall work with 24/7 support. 10/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to dial out 5/11/2022