                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        2.5 - Housekeeping
                     | 
                    
                        8.6.4.8 Machine Rooms and Machinery Spaces
                     | 
                    
                     | 
                    
                     | 
                    
                        Remove all unrelated storage from elevator equipment room.
                     | 
                    
                        11/17/2020
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Emergency phone does not work.
                     | 
                    
                        6/15/2022
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Phone in elevator cab is not working, line problem. Re-inspection required
                     | 
                    
                        4/11/2023
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The elevator ADA telephone inside the elevator is not operating  correctly. Check and repair the programming of this phone for proper operation and passenger safety.  Reinspection required in 14 days.
                     | 
                    
                        5/21/2024
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The elevator ADA phone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. Re-inspection required
                     | 
                    
                        6/13/2024
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The elevator ADA telephone inside the elevator is not operating correctly. Check & repair the programming of this phone for proper operation and passenger safety. Re-inspection required
                     | 
                    
                        7/3/2024
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Emergency phone is not operating correctly. Re-inspection required
                     | 
                    
                        8/23/2024
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                            x
                     | 
                    
                        The elevator ADA telephone inside the elevator is not operating correctly. Check and repair programming of the phone for proper operation and passenger safety. Note: This phone has not been operational since 6/2022. Elevator Red Tagged due to this issue.
                     | 
                    
                        10/1/2024
                     | 
                
                
                    | 
                        ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators
                     | 
                    
                        1.17 - Standby power operation
                     | 
                    
                        2.27.2
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Emergency power needs to be tested. Re-inspection required
                     | 
                    
                        4/9/2025
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        11 CSR 40-5.090 Inspection and Testing
                     | 
                    
                        (3) Testing Procedures (Re-Inspect)
                     | 
                    
                            x
                     | 
                    
                            x
                     | 
                    
                        Test failed, need to perform the following tests to complete Cat 5 full load test: Test car safeties with rated load at rated speed, test governor rope pull thru force, Perform unintended movement test. Test drive machine brake with 125% of rated load. Phase I & II fire service. Unit Red-tagged, Re-inspection required
                     | 
                    
                        8/23/2024
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        11 CSR 40-5.090 Inspection and Testing
                     | 
                    
                        (3) Testing Procedures (Re-Inspect)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The following tests need to be performed to complete inspection: full load, full speed safeties, unintended movement, fire service, safeties pull out, governor pull thru & 125% brake. Re-inspection required
                     | 
                    
                        7/3/2024
                     |