Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Provide a written Maintenance Control Program in the machine room. 4/23/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.34 - Flexible Hydraulic Hose and Fitting Assemblies 8.11.3.1.2 (q) aReplace the flexable hydraulic hose in the machine room, place a metal tag on the new one to show the installer, rated pressure date installed, and when it should be replaced again, the manufactuer etc. 4/15/2019