Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication inoperable. Re-inspection required 3/30/2022
conversion conversion n/a 3. During the inspection/testing process, in determining the tripping speed of the governor using Table 2.13.2. It was noted that the tripping speed that is stamped on the governor marking plate, is incorrect and shall be replaced with the proper data plate for governor. 7/23/2018
conversion conversion n/a 2. A permanent, safe, and convenient means of access to machine rooms and machinery spaces shall be provided and maintained. The 1st and 2nd wooden steps leading to machine space on upper level are split and shall be replaced. 7/23/2018
conversion conversion n/a 4. Control and operating circuits and devices shall be maintained in compliance with applicable Code requirements. Pit inspection operation device doesn?t function, it shall work or be removed. 7/23/2018
conversion conversion n/a 1. Horizontally sliding or single section swinging doors of automatic elevators must be provided with door closers arranged to close an open door automatically if the car leaves the landing zone for any reason. During inspection the 2nd floor (3rd Landing) door wasn?t free enough to pass the door closing inspection. 7/23/2018