ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency return unit inoperable and shall be repaired or replaced.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Means of two-way communication are inoperable and shall be repaired or replaced.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.1.4(l)
|
x
|
x
|
Repair Phase I fire recall. Car stop switch not overridden during Phase I recall. Did NOT red tag.
|
10/29/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6
|
x
|
|
In car keyed stop switch is not overridden on Phase I fire recall.
|
10/27/2021
|
conversion
|
conversion
|
n/a
|
|
|
ERU batteries leaking, no voltage present, replace batteries
|
10/29/2021
|
conversion
|
conversion
|
n/a
|
|
|
In-car stop switch not bypassed on Phase 1 recall, repair
|
10/29/2021
|