Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) x x Repair Phase I fire recall. Car stop switch not overridden during Phase I recall. Did NOT red tag. 10/29/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x In car keyed stop switch is not overridden on Phase I fire recall. 10/27/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency return unit inoperable and shall be repaired or replaced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Means of two-way communication are inoperable and shall be repaired or replaced.
conversion conversion n/a ERU batteries leaking, no voltage present, replace batteries 10/29/2021
conversion conversion n/a In-car stop switch not bypassed on Phase 1 recall, repair 10/29/2021