A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. Reinspection is required.
|
11/5/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power needs to be tested.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not give location and the recording says that it is not an emergency and is a test call.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.14.1.7 Railing and Equipment on Top of Cars
|
x
|
|
The cartop handrails are loose and shall be tightened.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell does not work.
|
12/17/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide written maintenance control program on site for each elevator.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell in elevator does not work, Re-inspect in 30 days
|
5/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
|
|
The emergency power indicating jewel failed to operate when activated, repair light jewel to activate as required.
|
|