Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) No No The emergency power indicating jewel failed to operate when activated, repair light jewel to activate as required. 11/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide written maintenance control program on site for each elevator. 11/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Alarm bell in elevator does not work, Re-inspect in 30 days 5/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Alarm bell does not work. 12/17/2021
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) Yes No The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. Reinspection is required. 11/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency power needs to be tested. 2/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not give location and the recording says that it is not an emergency and is a test call. 2/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 2.14.1.7 Railing and Equipment on Top of Cars Yes No The cartop handrails are loose and shall be tightened. 2/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency power needs to be tested. 11/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 2.14.1.7 Railing and Equipment on Top of Cars Yes No The cartop handrails are loose and shall be tightened. 11/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency power needs to be tested. 12/2/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.17.15 Yes No Governor reset solenoid is not functioning and needs repaired/replaced. 4/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency two-way communication device is not functioning and needs repaired. 4/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.1 Yes No Counterweight runby is greater than minimun distance allowed, blocking must be installed to achieve proper runby of 6" 4/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Yes No Emergency power jewel must be checked when emergency power is tested. 4/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.16.8 Yes No Emergency power operation must be tested. 4/6/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Break test, setting of safties, unintended motion, and ascending overspeed must be completed to satisfy full cat 5 test. These things could not be done due to repair needed on the governor reset solenoid. 4/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.16.8 Yes No Emregency power and emergency power jewel operations could not be tested due to faliure of generator operation.