Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell does not work. 12/17/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell in elevator does not work, Re-inspect in 30 days 5/26/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not give location and the recording says that it is not an emergency and is a test call.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power needs to be tested.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide written maintenance control program on site for each elevator.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 2.14.1.7 Railing and Equipment on Top of Cars x The cartop handrails are loose and shall be tightened.
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) x The elevator hoisting ropes are showing a high degree of wear and shall be replaced. Replace ropes within 30 days of inspection. Reinspection is required. 11/5/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) The emergency power indicating jewel failed to operate when activated, repair light jewel to activate as required.