Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide written maintenance control program on site for each elevator. 11/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) No No The emergency power indicating jewel failed to operate when activated, repair light jewel to activate as required. 11/21/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No A17.1 2016 8.6.4.16 The elevator car when landing at the 2nd floor is approximately 1/2” high and shall be adjusted to level in appropriately. 11/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency power shall be tested. 11/21/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.17.15 Yes No Governor reset solenoid is not fuctioning and must be repaired/replaced 4/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-way emergency communication device is not functioning and needs repaired. 4/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency power needs to be tested. 4/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Yes No The emergency power jewel must be check when emergency power is tested. 4/6/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Break test, setting of car safties, unintended movement, asending overspeed and emergecny power testing must be completed to satify full cat 5 test. This could not be completed due to repair needed for the governor reset solenoid. 4/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.16.8 Yes No Emergency power operation and emergency power jewel operations could not be tested due to failiure of genteration operation.