A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.3.1.1(e)
|
|
|
cab ceiling lights should be guarded to contain glass in case of breakage, drop ce3iling is open egg crate type
|
5/12/2022
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
8.11.3.1.3(b)
|
|
|
car top work light bulb is burnt out, replace bulb
|
5/12/2022
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection)
|
x
|
|
fire service phase 1 audible signal did not work
|
5/12/2022
|
A17.1-1996 : Elevators
|
3.27 - Crosshead data plate
|
207.3
|
|
|
Need to have a crosshead data tag, provide crosshead data tag
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
need to remove oil pumpback unit from pit
|
6/24/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no current cirt of operation displayed
|
6/24/2021
|
A17.1-2016 : Elevators
|
2.33 - Tanks
|
8.11.3.1.2(u)
|
|
|
oil level is low, cavitate when leveling into the top landing
|
5/12/2022
|
A17.1-1996 : Elevators
|
3.9 - Floor and emergency identification numbering
|
100.7
|
|
|
Provide floor numbers on both sides of landing entrance frame with braille indicating the floor designation
|
|