MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
car door restrictor not working
|
3/23/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self closing 2.7.3.4
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Replace burnt out pit light 2.2.5
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
Door restrictor missing part to catch the hook, repair door restrictor so it works
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.27 - Crosshead data plate
|
2.16.3
|
|
|
Did not have crosshead data tag
|
10/9/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
Replace burnt out pit light
|
10/9/2023
|
A17.1-1996 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
303
|
|
|
no mach.room shutoff valve
|
10/1/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
no curren cirt. of operation displayed
|
6/24/2021
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.3.1.1(e)
|
|
|
cab deiling light should be guarded to contain glass in case of breakage, open egg crate drop ceiling
|
5/12/2022
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
8.11.3.1.2(b)
|
|
|
repair machine room door self closer
|
5/12/2022
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.11.3.1.5(a)
|
|
|
pit light bulb is burnt out, replace bulb
|
5/12/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Did not have crosshead data tag 2.16.3
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency light battery is dead, install new battery
|
10/9/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone did not work, the number dialed goes straight to busy signal, reprogram phone to call a phone number that is answered 24 hours a day and 7 days a week - reinspection
|
10/9/2023
|