| ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 3.28 - Counterweight and counterweight buffer | 8.11.2.1.3(m) |  |  | replace missing counterweight slide guide insert |  | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 2.41 - Maintenance Records | 8.6.1.4 |  |  | Perform monthly fire service test and post test log in the machine room |  | 
                
                    | A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) |  |  | machine room fire extinguisher inspection tag is from 2017, needs to be inspected and tagged annualy |  | 
                
                    | A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | the copy of the state operating certificate posted in the machine room is to be updated annually |  | 
                
                    | MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | the state operating certificate on display in the machine room expired in 2017, update with current certificate when received from the state |  | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | machine room state operating certificate is from 2017, update with new copy when received from the state annualy |  | 
                
                    | ASME A17.1 2004 with 2005 Addendum and 2005  : Elevators | 2.18 - Traction drive machines | 8.11.2.1.2(p) | x |  | Loud noise coming from the drive machine (sounds like a bad bearing). |  |