conversion
|
conversion
|
n/a
|
|
|
Provide code compliant machine room lighting.
|
9/6/2018
|
conversion
|
conversion
|
n/a
|
|
|
Provide a complete set of controller prints.
|
9/6/2018
|
conversion
|
conversion
|
n/a
|
|
|
Provide a maintenance control program.
|
9/6/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on-site maintenance documents.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.11.2.1.2(e) (Re-Inspection)
|
|
|
The machine room shall not be used for storage of non-elevator related materials.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
The pit lighting shall be operational.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.2 - Stop switches
|
8.11.2.1.1(b) (Re-Inspection)
|
|
|
The in car stop switch shall be keyed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
The pit shall be cleaned.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
|
|
Fire tabs are missing on the bottom of all hoistway doors.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
Lighting is required in the elevator pit.
|
|