Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Provide code compliant machine room lighting. 9/6/2018
conversion conversion n/a Provide a complete set of controller prints. 9/6/2018
conversion conversion n/a Provide a maintenance control program. 9/6/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance documents.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.11.2.1.2(e) (Re-Inspection) The machine room shall not be used for storage of non-elevator related materials.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits The pit lighting shall be operational.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.2 - Stop switches 8.11.2.1.1(b) (Re-Inspection) The in car stop switch shall be keyed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be cleaned.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 Fire tabs are missing on the bottom of all hoistway doors.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Lighting is required in the elevator pit.