Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light shall work when unit is in backup power. Re-inspection required 10/29/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light shall work when unit is in backup power. Re-inspection required 11/12/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Emergency power indicator light shall work when unit is in backup power
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform testing of the following to complete 5 year inspection: 125% brake, counterweight buffer full load, full speed, car buffer full load, full speed, car safeties full load, full speed, emergency light in car, emergency alarm in car, emergency phone in car. Re-inspection required 11/12/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x x Overspeed governor tested excessive pull thru. Red-tagged, removed from service. Need to replace governor and governor rope and re-test, including pull thru, switch tripping speed and jaw tripping speed 11/12/2025