MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
x
|
x
|
Overspeed governor pull thru exceeded maximum allowable. Red-tagged and removed from service, need to acquire alteration permit and perform alteration inspection.
|
1/21/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power indicator light shall work when unit is in backup power. Re-inspection required
|
1/6/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power indicator light shall work when unit is in backup power. Re-inspection required
|
1/21/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power indicator light shall work when unit is in backup power. Re-inspection required
|
2/11/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following test to complete Cat 5 inspection after overspeed governor and rope is replaced: unintended movement, 125% brake, full load, full speed car buffer, full speed counterweight buffer & full load, full speed car safeties test to complete Cat 5 inspection. Re-inspection required
|
1/21/2026
|