Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x x Overspeed governor pull thru exceeded maximum allowable. Red-tagged and removed from service, need to acquire alteration permit and perform alteration inspection. 1/21/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light shall work when unit is in backup power. Re-inspection required 1/6/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light shall work when unit is in backup power. Re-inspection required 1/21/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light shall work when unit is in backup power. Re-inspection required 2/11/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform the following test to complete Cat 5 inspection after overspeed governor and rope is replaced: unintended movement, 125% brake, full load, full speed car buffer, full speed counterweight buffer & full load, full speed car safeties test to complete Cat 5 inspection. Re-inspection required 1/21/2026