ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power indicator light in fire panel shall work when unit is in backup power. Re-inspection required
|
1/21/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power indicator light in fire panel shall work when unit is in backup power. Re-inspection required
|
2/25/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power indicator light in fire panel shall work when unit is in backup power. Re-inspection required
|
3/4/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
|
|
Emergency power indicator light in fore panel does not work when unit is on backup power
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following tests to complete Cat 5 inspection: Unintended movement, 125% brake, full speed counterweight buffer, full load, full speed car buffer & full load, full speed car safeties. Re-inspection required
|
3/4/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
x
|
x
|
Overspeed governor exceeded maximum allowable pull thru, Red-tagged, removed from service. Need to replace governor and rope. Re-inspection required
|
2/25/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following tests to complete Cat 5 inspection: Unintended movement, 125% brake, full speed counterweight buffer, full load, full speed car buffer & full load, full speed car safeties. Re-inspection required
|
2/25/2026
|