Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Emergency power indicator light in fore panel does not work when unit is on backup power
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light in fire panel shall work when unit is in backup power. Re-inspection required 1/21/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x x Overspeed governor exceeded maximum allowable pull thru, Red-tagged, removed from service. Need to replace governor and rope. Re-inspection required 2/25/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform the following tests to complete Cat 5 inspection: Unintended movement, 125% brake, full speed counterweight buffer, full load, full speed car buffer & full load, full speed car safeties. Re-inspection required 2/25/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light in fire panel shall work when unit is in backup power. Re-inspection required 2/25/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform the following tests to complete Cat 5 inspection: Unintended movement, 125% brake, full speed counterweight buffer, full load, full speed car buffer & full load, full speed car safeties. Re-inspection required 3/4/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light in fire panel shall work when unit is in backup power. Re-inspection required 3/4/2026