Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light in fire panel shall work when unit is in backup power. Re-inspection required 1/21/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light in fire panel shall work when unit is in backup power. Re-inspection required 2/25/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency power indicator light in fire panel shall work when unit is in backup power. Re-inspection required 3/4/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Emergency power indicator light in fore panel does not work when unit is on backup power
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform the following tests to complete Cat 5 inspection: Unintended movement, 125% brake, full speed counterweight buffer, full load, full speed car buffer & full load, full speed car safeties. Re-inspection required 2/25/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform the following tests to complete Cat 5 inspection: Unintended movement, 125% brake, full speed counterweight buffer, full load, full speed car buffer & full load, full speed car safeties. Re-inspection required 3/4/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x x Overspeed governor exceeded maximum allowable pull thru, Red-tagged, removed from service. Need to replace governor and rope. Re-inspection required 2/25/2026