A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
x
|
Suspension means has damaged belt with broken strands exposed. Red-tagged, Re-inspection required
|
11/29/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power indicator light needs to work when on backup power. Re-inspection required
|
12/16/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
|
|
Emergency power indicator light needs to work when on backup power
|
|