MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
x
|
x
|
Overspeed governor failed pull thru test. Red-Tagged and removed from service, need to acquire alteration permit and perform alteration inspection when replaced.
|
1/21/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
|
|
Emergency power indicator light needs to work when on back-up power.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power indicator light needs to work when on backup power. Re-inspection required
|
1/6/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency power indicator light needs to work when on backup power. Re-inspection required
|
1/21/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following tests to complete Cat 5 inspection after governor and rope are replaced: unintended movement, 125% brake, full speed counterweight buffer, full speed, full load car buffer & full speed, full load car safeties. Re-inspection required
|
1/21/2026
|