Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current state operating certificate not displayed in machine room 3/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency light does not illuminate 7/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency light does not illuminate 1/13/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 HOISTWAYS SHALL HAVE FLOOR NUMBERS, NOT LESS THAN 4'' IN HEIGHT, ON THE HOISTWAY SIDE OF THE ENCLOSURE OR HOISTWAY DOORS
A17.1-2016 : Elevators 2.33 - Tanks 8.6.5.7 monitor use of hydraulic oil with written log in machine room. 3/15/2021
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 need to empty overflowing pit can. 3/15/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No maintenance control plan on site 3/21/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No maintenance records on site 3/21/2023
conversion conversion n/a Plunger packing leaks excessively. Replace plunger seal. 8/5/2019
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) post emergency evacuation of passengers form inside machine room 3/15/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys (Re-Inspection) x provide firefighter key in machine room or on site . 4/12/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits remove oil and oil soaked absorbent pads from pit. 3/15/2021
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Room and Machinery Space remove rags from machine room floor. 3/15/2021