Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers No No provide a cover for the pit sump pump. 2/23/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No provide a record of findings for firefighters' service operation 2/23/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.11.1 No No Need to perform and post monthly fire service test log in the elevator machine room 2/23/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No provide a ABC type fire extinguisher in or near the machine room, could not find a fire extinguisher 2/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No The Maintenance Control Program (MCP) On-Site documents are not in the machine room. 1/28/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No The firefighters service test log is not being filled out monthly. 1/28/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No The next overspeed valve test will be in 2025 1/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No both of the car top work lights are burnt out, replace bulbs 1/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Maintenance Control Program (MCP) documents are not in the machine room 10/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces No No Do not store non Elevator related items in the machine room 10/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Provide Fire extinguisher in the machine room 10/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.1.4(l) Yes Yes elevator did not return to the recall floor when the phase 1 keyswitch was turned to the on position, it stayed in normal operation. reset the parameters so that fire service works. 1/15/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No the emergency phone did not work, provide working phone line to the elevator controller 3/12/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No alarm bell failed 4/2/2021