|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.42 Seismic (Earthquake protection)
|
8.4.10
|
|
|
Seismic audio and visual alarm in the car is not working (seismic is activating in controller)
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.16 - Traveling cables and junction boxes
|
2.8.1
|
|
|
Traveling cable is damages and needs repair or replaced
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
2.14.7
|
|
|
Car Top Light not working.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.2
|
x
|
|
Runby is 3", roped need shortened
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
The call cancel button on Phase 2 fire service shall be operational. Expected date of completion: 4/8/2020 per Schindler Elevator.
|
7/15/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.11.2.1.2(e) (Re-Inspection)
|
|
|
Remove all non elevator related equipment from the machine room.
|
3/9/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
Provide operational machine room lighting.
|
11/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
The fire extinguisher in the elevator machine room is expired. A current tested ABC type fire extinguisher shall be provided in the machine room.
|
11/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
Clean the pit of dirt and debris.
|
11/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
A monthly fire service testing log shall be maintained and stored in the machine room.
|
11/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post the current state operating certificate in the elevator machine room.
|
11/22/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post operating certificate inside elevator equipment room.
|
11/22/2025
|