Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys All elevators in the same building shall have firefighter keyswitches operated by the same key. Need to install FEO-K1 keyswitches.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Post emergency evacuation of passengers procedure inside machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation Test and log firefighter operation monthly
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x CAR DOOR RESTRICTOR HAS BEEN REMOVED. REPLACE AND ADJUST TO OPERATE AS BUILT
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x CAR DOOR RESTRICTOR HAS BEEN REMOVED. REPLACE AND ADJUST TO OPERATE AS BUILT