Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger pump from pit
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light does not operate 10/8/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate 10/8/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm not working, phone ok. 11/13/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove rags, wooden blocks, and oil soaked absorbent pads from machine room floor.
MO Minimum : Elevators (I) - Pits (I)1 Need to remove standing oil in elevator pit. Pits need to be kept dry. 12/20/2019
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys All elevators in the same building shall have firefighter keyswitches operated by the same key. Need to install FEO-K1 keyswitches.
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys Provide key for firefighter operation on site.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Provide annual testing of firefighter operation with licensed inspector present 10/8/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room.