MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.11.1 Firefighters' Emergency Operation & Documentation
|
|
|
Fire service testing log not up to date.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)2 Alterations
|
|
|
Fire sprinkler added in machine room during remodeling work. Remove, or provide a shunt trip device and heat detector in machine room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. Bldg line.
|
2/20/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working, alarm bell ok.
|
8/27/2024
|
MO Minimum : Elevators
|
(G)2-Alterations
|
8.7.2.14.2 Car Enclosure
|
x
|
|
Emergency phone dropping call after connection.
|
1/19/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Machine room needs 110v receptical
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Machine room needs 110v gfci outlet
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
|
|
Pit switch working, but incorrectly labeled.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Fire service works, but won't reset with the key after testing.
|
1/19/2021
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Shunt trip not overriding battery lowering. Needs relay added
|
4/1/2024
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. Line?
|
4/1/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
x
|
|
Sprinkler line for shunt trip not finished.
|
1/18/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
Top of hoistway smoke sensor recalls elevator to wrong floor. Relay needed
|
4/1/2024
|