Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.3 x Sprinkler line for shunt trip not finished. 1/18/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Line? 4/1/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Shunt trip not overriding battery lowering. Needs relay added 4/1/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Top of hoistway smoke sensor recalls elevator to wrong floor. Relay needed 4/1/2024
MO Minimum : Elevators (H) - Machine Rooms (H)8 Machine room needs 110v receptical
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Bldg line. 2/20/2024
MO Minimum : Elevators (H) - Machine Rooms (H)8 Machine room needs 110v gfci outlet
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working, alarm bell ok. 8/27/2024
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x Emergency phone dropping call after connection. 1/19/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x x Fire service works, but won't reset with the key after testing. 1/19/2021
MO Minimum : Elevators (I) - Pits (I)7 Pit switch working, but incorrectly labeled.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation Fire service testing log not up to date.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)2 Alterations Fire sprinkler added in machine room during remodeling work. Remove, or provide a shunt trip device and heat detector in machine room.