Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams No No Connection loose on controller starter box din rail. 3/26/2026
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No Emergency lights not working. 1/19/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not being answered 4/1/2024
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No Emergency phone not identifying location of call. 1/19/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) No No Emergency phone not identifying the location. 1/19/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working, alarm bell ok. 1/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working, alarm bell ok. 3/26/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working, alarm bell ok.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation No No Fire service testing log not up to date. 3/26/2026
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 No No Machine room door must be self-closing 3/26/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Overhead lighting in car inadequate, and unguarded. 3/26/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate in machine room. 3/26/2026
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No Provide covers for FFS modules in machine room. 3/26/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Shunt trip not overriding battery lowering. Need relay added 4/1/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No Top hoistway smoke sensor recalls elevator to wrong floor. Need relay added 4/1/2024