MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-WAY COMMUNICATION DEVICE SHALL WORK. (Dials repeatedly, never connects)
|
10/24/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.)
|
11/16/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean and free of excessive oil/debris. (Reported as compliant on 4/27/22, ) NOT compliant as of this inspection
|
11/16/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean, free of excessive debris and oil.
|
4/27/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
6.5.9.3 Phase 2 switch does not initiate auto-recall after turning from ON to OFF. All other functions are proper. (Works if switch wiring is "jiggled". repair properly)
|
10/24/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
2.26.12
|
|
|
Front/rear floor markings (PI, button braille, open/close buttons/hall braille) shall be consistent and properly labeled. Reinsp 30days
|
9/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
telephone will not call out
|
7/29/2018
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly.
|
4/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly.
|
7/12/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly.
|
9/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Machine Room Fire Extinguisher shall have current monthly/annual test tag. Expired
|
4/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6
|
x
|
|
ire Service "reset" shall work properly Reinspect within 30days
|
9/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
x
|
x
|
Fire Service "reset" shall work properly Reinspect within 30days
|
9/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
x
|
x
|
Front/rear floor markings (PI, button braille, open/close buttons/hall braille) shall be consistent and properly labeled. Reinsp 30days
|
9/11/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. (Cert on display expired 2019)
|
11/16/2022
|