MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. (Water and oil accumulating, and sump pump does not work)
|
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
The upper packing on the two stage jack is leaking oil on both sides. Oil can be seen dripping down the piston.
|
|
A17.1-2016 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
8.11.3.1.2(w)
|
|
|
8.6.5.14.2 Supply pipe connected to the valve is dripping oil.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The Emergency Light does not work when normal power is removed
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit needs to be cleaned. All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
The oil supply pipe connected to the control valve needs to be tightened. It is steadily dripping oil.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.1 Means of Communication (Red Tag)
|
|
|
Occupant in car cannot hear front desk operator
|
1/5/2021
|