Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency light battery is dead and needs to be replaced 8/30/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.7 - Car door or gate 2.14.4 Yes No Repair bent pick up roller assembly on landing one hoistway door (2.14.4.2.4) 8/30/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No provide complete MCP in the machine room addording to code 6/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 No No Repair AC unit and maintain manufacturer's recommended operating range 6/16/2026
A17.1-2016 : Elevators 2.6 - Ventilation 8.11.2.1.2(i) No No the controller room air conditioner does not appear to be working, repair the air conditioner so the room is maintained at the recommended temperature per the manufacturer's data tag (2.7.9.2) 6/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 No No machine room air conditioner is not working, repair air conditioner so machine room is maintained at the manufacturer's recommended temperature range and humidity 6/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 No No Machine room air conditioner is not working, repair air conditioner so room is maintained at the manufacturer's recommended temperature range 6/16/2026
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(j) No No Machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually. 6/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) No No replace car top light bulb, it was burnt out 6/16/2026
A17.1-2016 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) No No bottom landing hoistway access keyswitch is not working 6/16/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.11.2.1.5(a) No No replace pit light bulb, it is burnt out 6/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No post monthly fire service test log in the machine room 6/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No post current copy of state operating certificate in the machine room 6/16/2026
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No the copy of the state operating certificate posted in the machine room is to be updated annually 6/16/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019 6/16/2026