Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The Category 5 testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 Yes Yes Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that the activation would not set with any sort of consistency. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. 6/5/2026