Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.37 - Pressure Switch 8.11.3.2.5 Pressure Switch (Re-Inspection) x The hydraulic pressure switch operation on the elevator controller would not activate when low oil pressure was detected. Repair the controller to operate as required. Reinspection required in 30 days. 3/11/2020