Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals x Must repair /replace left jack packing gland to limit leakage. 8.6.5.5 11/17/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit must be kept free of Oil. 8.6.4.7 11/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches Must make both top and bottom floor Hoistway access key switches operable. 8.6.4.14