A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
1001.2(a)(16)
|
|
|
Need to post "C-1 Loading No Passenger" sign inside elevator.
|
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
1001.2(a)(16)
|
|
|
Need to post "C-1 Loading No Passengers" sign inside elevator. Lettering to be a minimum of 1/2 inch high.
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Test and log firefighter operation monthly
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Post firefighter operating instructions next to hall fire keyswitch
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Post emergency evacuation of passengers form inside machine room
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate inside machine room
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Remove debris from pit
|
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
215
|
|
|
Post code data plate "A17.1 1996" on controller or disconnect.
|
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
207
|
|
|
Post sign on elevator. "C-1 LOADING. THIS ELEVATOR DESIGNED TO TRANSPORT LOADED INDUSTRIAL TRUCK. MAXIMUM COMBINED WEIGHT OF INDUSTRIAL TRUCK AND LOAD NOT TO EXCEED 10000 LB"
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Remove debris from the elevator pit.
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Test and log firefighter operation monthly.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside the machine room.
|
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Machine room access door needs to be self-locking
|
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.1a
|
|
|
Repair holes in machine room ceiling to maintain fire rating of the machine room.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No maintenance control plan in the machine room
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
No maintenance record log in the machine room
|
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
101.3d
|
|
|
Machine room access door shall be self-locking and non-defeatable
|
|
A17.1-1996 : Elevators
|
2.4 - Machine space
|
101.1a
|
|
|
Repair penetrations in machine room cieling.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No MCP
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
No maintenance records on site
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed in machine room
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell does not operate
|
9/22/2021
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
Car emergency light does not operate
|
9/22/2021
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.8 Switch Keys
|
|
|
All elevators in the same building shall have firefighter keyswitches keyed the same.
|
9/13/2022
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light does not illuminate
|
9/13/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell does not operate
|
9/13/2022
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.8 Switch Keys
|
|
|
All elevators in the same building shall have firefighter keyswitches operated by the same key.
|
9/13/2022
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light does not illuminate
|
9/12/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell does not operate
|
9/12/2023
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.8 Switch Keys
|
x
|
|
Firefighter keyswitches shall be operable using the same key as the other elevators in the building
|
9/12/2023
|