Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 1001.2(a)(16) Need to post "C-1 Loading No Passenger" sign inside elevator.
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 1001.2(a)(16) Need to post "C-1 Loading No Passengers" sign inside elevator. Lettering to be a minimum of 1/2 inch high.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate 9/13/2022
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Repair holes in machine room ceiling to maintain fire rating of the machine room.
A17.1-1996 : Elevators 2.4 - Machine space 101.1a Repair penetrations in machine room cieling.
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room access door shall be self-locking and non-defeatable
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room access door needs to be self-locking
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Remove debris from the elevator pit.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light does not illuminate 9/13/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency light does not illuminate 9/12/2023
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 207 Post sign on elevator. "C-1 LOADING. THIS ELEVATOR DESIGNED TO TRANSPORT LOADED INDUSTRIAL TRUCK. MAXIMUM COMBINED WEIGHT OF INDUSTRIAL TRUCK AND LOAD NOT TO EXCEED 10000 LB"
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Post firefighter operating instructions next to hall fire keyswitch
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys All elevators in the same building shall have firefighter keyswitches keyed the same. 9/13/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys All elevators in the same building shall have firefighter keyswitches operated by the same key. 9/13/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys x Firefighter keyswitches shall be operable using the same key as the other elevators in the building 9/12/2023
A17.1-1996 : Elevators 2.14 - Code data plate 215 Post code data plate "A17.1 1996" on controller or disconnect.
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate 9/12/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed in machine room
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate inside machine room
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Post emergency evacuation of passengers form inside machine room
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No MCP
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No maintenance control plan in the machine room
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No maintenance record log in the machine room
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No maintenance records on site
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Test and log firefighter operation monthly
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Test and log firefighter operation monthly.
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x Car emergency light does not operate 9/22/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate 9/22/2021
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Remove debris from pit