Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Car safeties need to be tested after safety drum rope is replaced. Re-inspection required 9/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x Elevator safety drum rope was replaced at some point in time with a non code conforming material. Safety drum rope must be of a corrosion resistant non ferrous material and not of tiller rope construction. Re-inspection required 9/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired. Replace or have serviced
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 Install crosshead data plate with correct speed (200 fpm)
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to test elevator for operation on emergency power. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 Observed numerous ledges exceeding 4”code requirement, repair as needed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Post Phase I instructions near the f/f switch in the lobby.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.27 - Crosshead data plate 2.16.3 Provide correct car speed on the cross head data plate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 x Provide testing of the elevator emergency power selector switch, located next door in the security office. 10/8/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of the elevator on emergency power. 10/8/2024