MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevator car safeties need to be tested after safety drum rope has been replace with proper material. Re-inspection required
|
9/13/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to test elevator for operation on emergency power. Re-inspection required
|
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)4
|
|
|
Install crosshead data plate with correct speed (200 fpm)
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
|
|
Observed numerous ledges exceeding code requirement of 4”, repair as needed.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.27 - Crosshead data plate
|
2.16.3
|
|
|
Provide correct car speed on the cross head data plate.
|
|
A17.1-2016 : Elevators
|
11.11 - Emergency Brake
|
2.19.3
|
|
|
Emergency brake failed to stop car within allowable 48" during unintended movement test. Repair & re-test. Re-inspection required.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Provide testing of the elevator on emergency power.
|
10/8/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
x
|
|
Provide testing of the emergency power selector switch. Located next door in the security office.
|
10/8/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
|
|
Post Phase I instructions near the f/f switch in the lobby.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.1.1
|
|
|
Cover up hole in machine room that leads to the pit and hoistway
|
11/4/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room is expired. Have serviced or replaced
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
x
|
|
Elevator safety drum rope was replaced at some point in time with a non code conforming material. Safety drum rope must be of a corrosion resistant non ferrous material and not of tiller rope construction. Re-inspection required
|
9/13/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Shorten suspension cables to get a minimum of 6 inches of counterweight runby. Re-inspection required
|
|