Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) x Fire service jewel on first floor shall be replaced. Re-inspection required 3/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x Battery backup system shall be made operable. Re-inspection required 3/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.11.3.2.2 Cylinders x x Packing on cylinder needs to be replaced within 90 days. Clean oil from pit and reinspect. Did not red tag. 6/30/2021