MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher in machine room is expired, have serviced or replace
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Provide testing of the elevator on emergency power.
|
10/9/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to test elevator for operation on emergency power. Re-inspection required
|
|
A17.1-2016 : Elevators
|
11.11 - Emergency Brake
|
2.19.3
|
x
|
|
Emergency brake failed to stop car within allowable distance when performing unintended movement test, repair and re-test. Re-inspection required
|
9/12/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
x
|
|
Provide testing of the emergency power selector switch. Located next door in the security office.
|
10/9/2024
|