Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 11.11 - Emergency Brake 2.19.3 Yes No Emergency brake failed to stop car within allowable distance when performing unintended movement test, repair and re-test. Re-inspection required 9/12/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Provide testing of the elevator on emergency power. 10/9/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 Yes No Provide testing of the emergency power selector switch. Located next door in the security office. 10/9/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to test elevator for operation on emergency power. Re-inspection required 10/1/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Shorten suspension cables to get a minimum of 6" of counterweight runby 4/10/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Front door restrictor is not working. Re-inspection required 4/10/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to test elevator for operation on emergency power. Re-inspection required 4/10/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, have serviced or replace 10/1/2025