Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 11.11 - Emergency Brake 2.19.3 x Emergency brake failed to stop car within allowable distance when performing unintended movement test, repair and re-test. Re-inspection required 9/12/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of the elevator on emergency power. 10/9/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 x Provide testing of the emergency power selector switch. Located next door in the security office. 10/9/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to test elevator for operation on emergency power. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired, have serviced or replace