Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a 1. Control and operating circuits and devices shall be maintained in compliance with applicable Code requirements. There are two floor call buttons that are not servicing a floor stop, they shall be removed. 4th and 5th floor buttons. 8/28/2018
conversion conversion n/a 2. When an emergency stop switch or alarm button is provided, an audible signaling device shall be provided. The audible signaling device shall have a rated sound pressure rating of not less than 80 dBA nor greater than 90 dBA at 10 ft. Audible signaling device can barely be heard. 8/28/2018