ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Machine room access door needs to be self-locking.
|
9/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Post emergency evacuation of passengers form inside machine room.
|
9/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Test fire service operation monthly and provide documentation.
|
9/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.14.1.7 Railing and Equipment on Top of Cars
|
|
|
Install top of car handrail. Clearance from edge of the cartop to hoistway wall exceeds 12 inches
|
10/18/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.14.1.7 Railing and Equipment on Top of Cars
|
|
|
Top of car handrail does not have 4 inch toe board and top rail is only 36 inches in height. Overhead allows for handrail that is 42 inches in height.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.31 - Relief Valves
|
3.19.4.2 (Pump Relief Valve)
|
|
|
RELIEF VALVE IS SET TOO HIGH. IT IS SET AT 570PSI AND SHOULD NOT EXCEDE 537PSI AS PER TAG ON UNIT
|
|