Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency lowering device shall be operational. 6/21/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.1.3 Provide Auxiliary Lighting x Make emergency light operational. 7/29/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No wiring diagram in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 7/29/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 8.11.2.1.2(l) Up-to-date wiring diagrams shall be provided on-site.
A17.1-2016 : Elevators 9.19 - Maintenance Records 8.6.1.2.1(a) Wiring prints and maintenance logs shall be kept on-site.