ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
4/29/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures, maintenance charts, and fire service monthly testing log are missing.
|
2/13/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.4 Means for Manual Release
|
|
|
Means to release brake shall be operational (UPC Unit).
|
2/13/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
The pit shall be kept clean. Clean the pit.
|
2/13/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
Hoistway door safety retainers/fire tabs shall be installed at the bottom of all hoistway doors.
|
3/21/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency lighting shall work.
|
3/21/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Fire service testing shall be documented monthly.
|
3/21/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
The pit shall be kept clean. There are puddles of oil around rails/debris.
|
3/21/2024
|