Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Machine room light switch shall be a mechanical switch. 8/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x The auxiliary power lowering operation shall be functional. An uninterruptible power supply for the emergency lowering operation was sitting on the floor of the machine room. When an elevator is equipped with this device, it has to be operational and can't be removed without the permission of the MO AHJ. 7/22/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 3.26.10 (Auxiliary Power)(Re-Inspection) x The following violation cited in 2023 has not been corrected: The auxiliary power lowering operation shall be functional. An uninterruptible power supply for the emergency lowering operation was sitting on the floor of the machine room. When an elevator is equipped with this device, it has to be operational and can't be removed without the permission of the MO AHJ. Note: This has auxiliary power unit has not yet been re-installed. See MO Memorandum 016 for more information regarding this violation. 1/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 x Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position.